    A fire door rating is the time a complete door assembly (door, frame, hardware and glazing) has withstood standard fire testing under NFPA 252 or UL 10C positive pressure. Typical ratings are 20 minutes for corridors and smoke barriers, 45 minutes for most 1-hour fire barriers, 60 or 90 minutes for 1-hour and 2-hour stair and shaft enclosures, and 3 hours for 3-hour fire walls and barriers. NFPA 80 governs installation and requires fire door assemblies to be inspected at least once a year.

    Fire Rating Classifications

    The required door rating depends on the type of wall and its fire-resistance rating under Section 716 of the Florida Building Code, and is often lower than the wall rating. Doors in interior exit stairway enclosures may also need a temperature-rise rating. Always confirm requirements with the design professional and the authority having jurisdiction.

    20 Minutes

    20-min

    Wall Type

    Corridor walls (fire partitions) and 1-hour smoke barriers

    Common Applications

    Corridor doors
    Smoke barrier doors
    Tested without hose stream

    Glazing Limit

    Fire-protection-rated glazing (D-20 marking) up to the maximum size tested and listed

    45 Minutes

    45-min

    Wall Type

    Most 1-hour fire barriers and fire partitions

    Common Applications

    Tenant separations
    1-hour occupancy separations
    Incidental use rooms

    Glazing Limit

    Fire-protection-rated glazing (D-H-45 marking) up to the maximum size tested and listed

    60 Minutes

    60-min

    Wall Type

    1-hour shaft, exit stairway and exit passageway enclosures

    Common Applications

    Exit stairways connecting fewer than 4 stories
    1-hour shaft enclosures

    Glazing Limit

    100 sq in of fire-protection-rated glazing, unless listed fire-resistance-rated glazing is used

    90 Minutes

    90-min

    Wall Type

    2-hour fire barriers, fire walls, shaft and exit stairway enclosures

    Common Applications

    Exit stairways connecting 4 or more stories
    2-hour shaft enclosures
    2-hour fire walls

    Glazing Limit

    Typically 100 sq in of fire-protection-rated glazing, unless listed fire-resistance-rated glazing is used

    3 Hours

    3-hr

    Wall Type

    3-hour and 4-hour fire walls and fire barriers

    Common Applications

    Fire walls
    3-hour fire barriers
    3-hour occupancy separations

    Glazing Limit

    Fire-resistance-rated glazing (D-H-W-180) to the maximum size tested; fire-protection-rated glazing only in horizontal exits, up to 100 sq in

    Fire Door Assembly Components

    A fire door is only as strong as its weakest component. Every part of the assembly must be labeled or listed for fire door use and properly installed.

    Fire Door

    Must bear a permanent label from an approved testing and listing agency

    Test Standard:NFPA 252 or UL 10C (positive pressure)
    Label Info:Rating, listing agency, serial or listing number, and temperature rise where applicable

    Fire Frame

    Must be labeled with a rating equal to or greater than the door it serves

    Test Standard:NFPA 252 or UL 10C, as part of the tested assembly
    Label Info:Maximum rating of the frame and listing agency

    Hardware

    Latches, closers and fire exit hardware must be listed for fire doors; hinges must meet NFPA 80 (steel, ball-bearing) or be listed

    Test Standard:UL 10C; fire exit hardware also UL 305
    Label Info:Listed hardware is marked by the manufacturer; fire exit hardware carries its own label

    Glazing

    Must be listed for use in fire doors at the required rating; safety glazing rules also apply

    Test Standard:NFPA 252 / UL 10C in doors; ASTM E119 / UL 263 for fire-resistance-rated glazing
    Label Info:Permanent mark with manufacturer and designation, such as D-H-90

    Gasketing

    Smoke and draft control gasketing where required, plus any edge seals the door's listing calls for

    Test Standard:UL 1784 (smoke and draft control), UL 10C (positive pressure)
    Label Info:Smoke and draft control assemblies are marked with an "S" label

    Fire Door Inspection Checklist

    NFPA 80 requires fire door assemblies to be inspected and tested at least annually, with written records. Use this checklist to prepare for inspections or self-audit your facilities.

    Annual Inspection Items (NFPA 80)

    Fire door label visible and legible
    Critical
    Frame label visible and legible
    Critical
    Door closes and latches completely from the full open position
    Critical
    Door closer operates properly
    Critical
    Clearances within tolerance (1/8" at head, jambs and meeting stiles, +/- 1/16" on steel doors; 3/4" max under the door)
    Critical
    No field modifications that void the label (unapproved holes, patches)
    Critical
    Glazing properly labeled if present
    Gasketing and edge seals present and intact where required
    Fire exit hardware operates properly (if applicable)
    No wedges or kick-down stops; hold-open devices are listed and release on alarm
    Critical

    Planning an installation? See our installation services and the Florida Building Code door guide.

    Common Fire Door Violations

    Avoid these frequent inspection failures that compromise life safety and result in code violations.

    Missing or illegible labels

    Consequence:

    The rating cannot be verified; the opening may need field inspection and relabeling by the listing agency, or replacement

    Prevention:

    Keep labels legible and mask them during field painting

    Door fails to latch

    Consequence:

    Must be corrected; swinging fire doors need an active latch to stay closed during a fire

    Prevention:

    Regular maintenance and hardware adjustment

    Unapproved modifications

    Consequence:

    Changes beyond those NFPA 80 permits can void the listing and require evaluation or replacement

    Prevention:

    Check with the manufacturer or listing agency (such as Intertek) before modifying a fire door

    Excessive clearances

    Consequence:

    Smoke and fire protection compromised; requires correction

    Prevention:

    Install and adjust per NFPA 80 and the manufacturer's instructions

    Blocked or wedged open

    Consequence:

    Fire code violation that defeats the purpose of the fire door

    Prevention:

    Use listed hold-open devices that release on fire alarm or smoke detection

    Fire Door Rating FAQs

    What fire rating does a commercial door need?

    The required rating depends on the wall the door is in. Typical ratings are 20 minutes for corridor walls and smoke barriers, 45 minutes for most 1-hour fire barriers and fire partitions, 60 minutes for 1-hour stair and shaft enclosures, 90 minutes for 2-hour walls and enclosures, and 3 hours for 3-hour and 4-hour fire walls and fire barriers.

    How often do fire doors have to be inspected?

    NFPA 80 requires fire door assemblies to be inspected and tested at least annually by a person with knowledge of the door's operating components, with written records kept for the authority having jurisdiction. New installations also require acceptance testing.

    What is positive pressure fire testing?

    Positive pressure testing under NFPA 252 or UL 10C places the furnace's neutral pressure plane no higher than 40 inches above the sill, so heat and flame push through the door edges as they would in a real fire. The Florida Building Code requires it for side-hinged and pivoted swinging fire doors, which is why many assemblies use intumescent edge seals.

    What is a temperature-rise fire door?

    A temperature-rise door limits the heat transmitted to the unexposed side during the first 30 minutes of the fire test, and its label shows the maximum rise, such as 250°F, 450°F or 650°F. Doors in interior exit stairway and exit passageway enclosures generally need a maximum 450°F rise, except in buildings equipped throughout with automatic sprinklers.

    Can a fire door be modified in the field?

    Only in limited ways. NFPA 80 permits certain jobsite work, such as holes for surface-applied hardware and installing labeled viewers or protection plates. Other modifications need approval from the manufacturer or listing agency and may require field inspection and relabeling.